INSTALLATION INSTRUCTIONS
351 EHTD Electromechanical Closer-Holder Device
DOUBLE EGRESS
CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR DAMAGE.
For assistance contact SARGENT at 800-810-WIRE (9473) or www.sargentlock.com
1
Right Hand
Shown
A7654A
1
NOTE: AN AUXILIARY DOOR STOP IS REQUIRED AT HOLD OPEN
CAUTION:
1. DISCONNECT ALL POWER BEFORE INSTALLATION
2. ALL WIRING TO BE PERFORMED BY QUALIFIED PERSONNEL TO
COMPLY WITH ALL APPLICABLE LOCAL CODES.
3. MAXIMUM WIRE SIZE IS 18 AWG.
!
2
351 closers are non-handed, RH must be on top for right hand
doors and LH must be on top for left hand doors.
3
Attach conduit adapter to track with nut provided.
Secure cable or conduit (by others) per local codes.
4
Secure track to frame with electronics toward hinge with screws
provided. Install hole plugs into exposed holes in track.
5
Connect 24VDC/VAC to terminal block marked “+”,
“-” and “GND” (if applicable). (NOTE: GND used if AC
is used.)
+
-
GND
On/Off
Switch
6
Use template from page 3; drill and tap door and frame for 12-24 machine screws and prepare hole for conduit.
Do not drill through channel, as damage will occur voiding warranty.
7
Use screw and washer to secure main arm to spindle with index
mark as shown.
Index
mark on
spindle
Index mark
on spindle
Positioning of arm when
assembling to spindle
Hinge
Hinge
R. H. Door
L. H. Door
Closer, Spindle, Washer
and Screw
Wire through fire alarm contact OR
optional “Remote Release” switch if used.
Fire alarm
contact by
others or
optional remote
release switch
R. H.
L. H.
Install closer body to door with spring power nut away
from hinge.
WARNING:
IF NOT PROPERLY INDEXED,
DOOR CLOSER WILL NOT
FUNCTION PROPERLY.
Hole Plug
Cover plate installed
after wiring
S
pring Power
Nut
Copyright © 2009, Sargent Manufacturing Company, an ASSA ABLOY Group
company. All rights reserved. Reproduction in whole or in part without the
express written permission of Sargent Manufacturing Company is prohibited.
Seitenansicht 0
1 2 3

Inhaltsverzeichnis

Seite 1 - DOUBLE EGRESS

INSTALLATION INSTRUCTIONS351 EHTD Electromechanical Closer-Holder Device –DOUBLE EGRESSCAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN IN

Seite 2 - 30-36 FACTORY SET FACTORY SET

Final Adjustment and Regulating ProceduresSLOWDOWNSPEEDUPDoor WidthExterior Doors Interior Doors(Inches)24-30 TURN nut 1-3 TURN nut 1-330-36 FACTORY S